Operating Mechanism
(15)
Would you like to get more Operating Mechanism informations, please call me, or click Inquiry Now to fill in the Form.
It helps you get more informations you need to trade confidently with suppliers.
Model No: MD.J19
This operating mechanism is sole used in ZN28-12kV Indoor VCB which mounted on 10kV handcart switchgear cabinet ,or other resemble Closing work of VCB. Its closing spring has two energy storage ways:electric energy storage and manual energy storage
There are three opening operations:opening magnet,over-current releaser,manual button.And two closing operations:closing magnet and manual button.
| Item | Weight(Kg) | Size(mm) | Rated input power of motor(W) | Closing spring(mm) | Rated short-circuit breaking current of Breaker(kA) |
| CD19-â… | 30 | 420×350×160 | 70 | φ7 | 20 |
| CD19-â…¡ | 30 | 420×350×160 | 90 | φ7.5 | 31.5 |
| CD19-â…¢ | 30 | 420×350×160 | 120 | φ8 | 40 |
| Model | 66ZY-CJ11 | |
| Rated work voltage | 110 | 220 |
| Rated input power of motor | 70.90.120 | |
| The voltage scope of normal work | 85%-110% of the rated voltage | |
| Energy storage times | ≤12s | |
| Rated work voltage(V) | ~110 | ~220 | ~380 | -48 | -110 | -220 |
| Rated work current(A) | 5 | 4.5 | 3.5 | 2.34 | 1.63 | |
| Rate work power(W) | <572 | <772 | <160 | <257 | <359 | |
| 20℃ resistance of coil(Ω) | 9.50.5 | 20.81 | 150.75 | 472.5 | 1857 | |
| The voltage scope of normal opening | 65%-120% of the rated voltage.It can't opening if less than 30% of rated voltage | |||||
| The voltage scope of normal closing | 80%-110% of the rated voltage | |||||
ModelNo:MD.J19B
This Mechanism is sole used in Chinese Model ZN28A-12kV or 40.5kV VCB which mounted on width of 350 ,10kV fixed switchgear cabinet,or other resemble Closing work of VCB.It also widely used in Chinese Model GG-1A.XGN2-12,ect.switchgear cabinet. Its closing spring has two energy storage ways: electric energy storage and manual energy storage.
There are three opening operations: opening magnet,over-current releaser,manual button.
And two closing operations: closing magnet and manual button.
The closing magnet use solenoid type magnet,the detail as belows:
Rated work voltage(V) |
∽110 | ∽220 | -48 | -110 | -220 |
| Rated work current(A) | 5 | 4.5 | 3.8 | 3.5 | 3.2 |
| Rate work power(W) | 374 | 330 | 158 | 319 | 220 |
| 20℃ resistance of coil(Ω) | 14.9±0.7 | 54±2.7 | 14.9±0.7 | 37±0.9 | 221.5±5.5 |
| The voltage scope of normal opening | 65%-120% of the rated work voltage.Can't opening if less than 30% of the rated work voltage | ||||
| The voltage scope of normal closing | 85%-110% of the rated work voltage | ||||
Model No: MD.J19BN
This operating mechanism is used in 12kV or 40.5kV Indoor Vacuum Circuit Breaker,or other resemble Closing work of SF6 Circuit Breaker , Mini-Oil Circuit Breaker,ect. Its closing spring has two energy storage ways:electric energy storage and manual energy storage. There are three opening operations:opening magnet,over-current releaser,manual button.
And two closing operations:closing magnet and manual button.
| Item | Unit | Date | |
| Closing work | J | 350-500 | |
| Energy-storage motor | Model | HDZ-220B | |
| Rated voltage or current | ≌V/1.6~1.8 | ||
| Rated output power | W | 120~160 | |
| Energy storage times | S | ≤15 | |
| Scope of work voltage | 85~110% of the rated voltage | ||
| Closing and Opening magnet | Rated work voltage | V | ~110V ~220V 380V -220V -110V |
| Rated work current | A | 5.6 4.5 2.1 2.03 4.07 | |
| 20℃ resistance of coil | Ω | 60±0.3 23±1.5 108±5.4 24±1.35 | |
| Scope of work voltage | Closing/opening magnet:85-110%/65-120% of rated voltage.Can't opening if less than 30% continuous three times | ||
| Auxiliary switch | Model | F11-12â…¢/L | |
| The number of NO contact | Pair | 6 | |
| The number of NC contact | |||
| Rated closing and opening current | A | AC12.5A ; DC220V 4A,110V 8A | |
| Output rotate angle | Degree | 50°-55° | |
| Mechanical life | Times | 10000 | |
| Closing time of Breaker | S | 0.030~0.060 | |
| Opening time of Breaker | 0.015~0.050 | ||
| No-current Gap-time of one shot reclosure | 0.3 | ||
| power frequency withstand voltage of Secondary circuit (1 min) | V | 2000 | |
Model No: MD.J19BW
This operating mechanism is used in 12kV or 40.5kV Pillar type Outdoor Vacuum Circuit Breaker,or other resemble Closing work of SF6 Circuit Breaker , Mini-Oil Circuit Breaker,ect. Its closing spring has two energy storage ways:electric energy storage and manual energy storage. There are three opening operations:opening magnet,over-current releaser,manual button.
And two closing operations:closing magnet and manual button.
Number |
Item | Unit | Date | |
| 1 | Closing work | J | 350-500 | |
| 2 | Energy-storage motor | Model | HDZ-220B | |
| Rated voltage or current | ≌V/1.6~1.8 | |||
| Rated output power | W | 120~160 | ||
| Energy storage times | S | ≤15 | ||
| Scope of work voltage | 85~110% of the rated voltage | |||
| 3 | Closing and Opening magnet | Rated work voltage | V | ~110V ~220V 380V -220V -110V |
| Rated work current | A | 5.6 4.5 2.1 2.03 4.07 | ||
| 20℃ resistance of coil | Ω | 60±0.3 23±1.5 108±5.4 24±1.35 | ||
| Scope of work voltage | Closing/opening magnet:85-110%/65-120% of rated voltage.Can't opening if less than 30% continuous three times | |||
| 4 | Auxiliary switch | Model | F11-12â…¢/L | |
| The number of NO contact | Pair | 6 | ||
| The number of NC contact | ||||
| Rated closing and opening current | A | AC12.5A ; DC220V 4A,110V 8A | ||
| 5 | Output rotate angle | Degree | 50°-55° | |
| 6 | Mechanical life | Times | 10000 | |
| 7 | Closing time of Breaker | S | 0.030~0.060 | |
| Opening time of Breaker | 0.015~0.050 | |||
| 8 | No-current Gap-time of one shot reclosure | 0.3 | ||
| 9 | power frequency withstand voltage of Secondary circuit (1 min) | V | 2000 | |