Operating Mechanism
(15)
Would you like to get more Vacuum Circuit Breaker informations, please call me, or click Inquiry Now to fill in the Form.
It helps you get more informations you need to trade confidently with suppliers.
Click here to download this product PDF.
The VMD1 series indoor circuit-breaker is our independent developed new generation 12 kv assemble pole kind vacuuum circuit breaker .
All the technical parameters of breaker completely satisfy the Standards Of GB1984 AC Highvoltage Breaker, GB/T 11022 -1999 Common Specifications For High-Voltage Switchgear And Controlgear Standards, China Power Sector Standards DL403.
Also meet the requirements of IEC62271-100, IEC56 and other main industrialized country’s similar standards
| NO | Item | Unit | Technical Date | |||||||
| 1 | Rated voltage | KV | 12 | |||||||
| 2 | Rated insulating level | Rated short time power frequency withstand voltage(1min) | 42 | |||||||
| Rated lighting inpulse withstand voltage (peak value) | 75 | |||||||||
| 3 | Rated Frequency | Hz | 50 | |||||||
| 4 | Rated current | A | 630 | 630 | 1250 | 1250 | ||||
| 1250 | 1250 | 1600 | 1600 | |||||||
| 2000 | 2000 | |||||||||
| 2500 | 2500 | |||||||||
| 3150 | 3150 | |||||||||
| 4000 | 4000 | |||||||||
| 5 | Rated short circuit breaking current | kA | 20 | 25 | 31.5 | 40 | ||||
| 6 | Rated short time withstand current | 20 | 25 | 31.5 | 40 | |||||
| 7 | Rated peak withstand current | 50 | 63 | 80 | 100 | |||||
| 8 | Rated short-circuit closing current (peak value) | 50 | 63 | 80 | 100 | |||||
| 9 | 4S rated short-time withstand current 4s | 20 | 25 | 31.5 | 40 | |||||
| 10 | Rated shock steady current | 50 | 63 | 80 | 100 | |||||
| 11 | Rated making surge current of capacitor bank | 12.5(The frequency is less than 1000Hz) | ||||||||
| 12 | Rated breaking current of single/symmetrical capacitor bank | A | 630/400 (The value shoule be 800/400 while the current is 40kA) | |||||||
| 13 | Duration of rated short-circuit current | S | 4 | |||||||
| 14 | Power frequency withstand voltage of secondary circuit | V | 2000 | |||||||
| 15 | Rated operationl voltage | Making coil | AC110/220 DC110/220 | |||||||
| Breaking coil | AC110/220 DC110/220 | |||||||||
| Energy-storage motor | AC110/220 DC110/220 | |||||||||
| 16 | Making time(under Rated voltage) | ms | 35-70 | |||||||
| 17 | Brealing time(under Rated voltage) | 20-45 | ||||||||
| 18 | Permitted abrasion thickness of moving and fixed contacts | mm | 3 | |||||||
| 19 | Energy storage times | S | ≤15 | |||||||
| 20 | Contactor space | mm | 9± 1 | |||||||
| 21 | Contacting travel | 3---4 | ||||||||
| 22 | Bounce time of Contactor during making | ms | ≤2 | |||||||
| 23 | Different time of breaking / making of 3 phases | ≤2 | ||||||||
| 24 | Average breaking speed 1 | 0.9-1.3 | ||||||||
| 25 | Average making speed 2 | 0.4-0.8 | ||||||||
| 26 | Rebound amplitude of contact breaking | mm | ≤3 | |||||||
| 27 | Conductance circuit resistance | μΩ | ≤50 (630A) | |||||||
| ≤45(1250A) | ||||||||||
| ≤35(1600A-2000A) | ||||||||||
| ≤25(More than 2500A) | ||||||||||
| 28 | The contacting pressure of contactor during making | N | 2000±200(20kA) | |||||||
| 2400±200(25kA) | ||||||||||
| 3100±200(31.5kA) | ||||||||||
| 4750±250(40kA) | ||||||||||
| 29 | Rated operating order | O- 180s -CO-180s-CO/O- 0.3s -CO-180s-CO | ||||||||