145kV Outdoor Double Side Break Disconnect Switch Substation Isolator Disconnector
Basic Info
Model No.: GW7B-145
Product Description
Model NO.: GW7B-145 Structure: Double-column Disconnector Operation: Electric Movement Mode: Horizontal Rotary Type Grounding: Single Ground Run: Turn the Horizontal Common Model: Gw4a Certification: ISO, GS, RoHS, CE, IS9001, ISO9001 Application: Outdoor Voltage rating: up to 420kV Trademark: Tianan Electric Specification: Center break HS Code: 8535300000 Type: High-voltage Installation: Outdoor High-voltage Grounding Mode: Grounding Number of Poles: Three Pole Series: Single-Stage Switching Mode: Single Throw-in Structure of Operating: Electric Brand: Tianan Standards: IEC, ANSI, GB Current rating: upto 4000A Transport Package: Wooden Case Origin: Ningbo, China General
GW7B Isolating Switch is a kind of outdoor HV electricity transmission Equipments at three-phase AC frequency of 50/60Hz. It is used for breaking or connecting HV lines under no loads so that these lines can be changed and connected and the way the electricity runs is changed. In addition, it can be used to exercise safe electrical insulation for such HV electric apparatuses as bus and breaker. The switch can open and close inductance/ capacitance current and is able to open the bus to switch current.
This product has three posts with horizontal open breaks. JW10 grounding switches may be attached to the product at one or two sides. 72.5~252kV isoalting siwtch adopts CJ2 or SRCJ2 manual actuator to realize the tri-ole linkage. The grounding switch adopts CS11 or SRCS manual actuator to actualize tri-pole linkage. 363kV isoalting switch adopts SRCJ2 motor's actuator to realize the single pole operation; while the grounding switch takes SRCS manual actuator or SRCJ2 motor's actuator to realize the single pole operation and also tri-pole linkage.
Technical data
Contact us if you need more details on Disconnector. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Isolator、Isolating Switch. If these products fail to match your need, please contact us and we would like to provide relevant information.
GW7B Isolating Switch is a kind of outdoor HV electricity transmission Equipments at three-phase AC frequency of 50/60Hz. It is used for breaking or connecting HV lines under no loads so that these lines can be changed and connected and the way the electricity runs is changed. In addition, it can be used to exercise safe electrical insulation for such HV electric apparatuses as bus and breaker. The switch can open and close inductance/ capacitance current and is able to open the bus to switch current.
This product has three posts with horizontal open breaks. JW10 grounding switches may be attached to the product at one or two sides. 72.5~252kV isoalting siwtch adopts CJ2 or SRCJ2 manual actuator to realize the tri-ole linkage. The grounding switch adopts CS11 or SRCS manual actuator to actualize tri-pole linkage. 363kV isoalting switch adopts SRCJ2 motor's actuator to realize the single pole operation; while the grounding switch takes SRCS manual actuator or SRCJ2 motor's actuator to realize the single pole operation and also tri-pole linkage.
Technical data
S/N | Item | Unit | Parameter | ||||
1 | Rated voltage | kV | 72.5 | 145 | 252 | 363 | 420 |
2 | Rated insulation level | | | | | | |
3 | Rated power frequency withstand voltage (1 min) | | | | | | |
4 | To earth | kV | 160 | 275 | 460 | 210 | 520 |
5 | Across open breaks | kV | 200 | 275+85 | 460+145 | 210+210 | 610 |
6 | Rated lightning impulse withstand voltage | | | | | | |
7 | To earth | kV | 350 | 650 | 1050 | 1175 | 1425 |
8 | Across open breaks | kV | 410 | 650+120 | 1050+200 | 1175+295 | 1425+240 |
9 | Rated switch impulse withstand voltage (peak) | | | | | | |
10 | between phase/ to earth | kV | -- | -- | -- | 1425/950 | 1574/1050 |
11 | Across open breaks | kV | -- | -- | -- | 850+295 | 900+345 |
12 | Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 |
13 | Rated current | A | 1250 2000 2500 3150 4000 | 1250/2000 | 2000 2500 3150 4000 5000 | 31,505,000 | 3150 |
14 | Rated short-time withstand current | kA | 40 50 | 31.5/40 | 50/63 | 160 | 160 |
15 | Rated peak withstand current | kA | 100 125 | 80/100 | 125/160 | 63 | 63 |
16 | Rated duration of short circuit | s | 4 | 4 | 3 | 3 | 2 |
17 | Rated terminal mechanical load | | | | | | |
18 | Horizontal -logntitudinal | N | 750/1000 | 1250 | 1500 | 2500 | 2000 |
19 | Horizontal- vertical | N | 500/750 | 750 | 1000 | 2000 | 660 |
20 | Vertical force | N | 750 | 1000 | 1250 | 1500 | 1500 |
21 | Isolating switch bus capacity of switching currents and opening/ closing | | 100V, 1600A, 100 times | 100V, 1600A, 100 times | 300V, 1600A, 100 times | 450V, 3200A, 3times 400V, 1600A, 100 times | 300V, 1600A, 100 times |
22 | Grounding switch induction current open/ closing capacity | | | | | | |
23 | Electromagnetic induction-typ current (current/ voltage) | A/kV | 100/4 (80/2) | 100/6 (80/2) | 160/15 (80/3) | 1250/35 (160/10) | 160/10 (80/2) |
24 | electrostatic induction current (current/ voltage) | A/kV | 2/6 | 5/6 (2/6) | 10/15 (3/12) | 50/50 (18/17) | 18/20 (1.25/5) |
25 | Times of opening and closing | times | 10 | 10 | 10 | 10 | 10 |
26 | isolating switch small current open/ closing capacity | | | | | | |
27 | capacitive current | A | -- | 1 | 1 | 1 | 1 |
28 | Inductive current | A | -- | 0.5 | 0.5 | 0.5 | 0.5 |
29 | RIV radio interference voltage | uV | <500 | <500 | <500 | <500 | <500 |
30 | Creepage distance | mm | >1813 2248 | >3625 4495 | >6300 7812 | >9450 | >10500 |
31 | Mechnical endurance | times | 5000 | 5000 | 1000 | 5000 | 10000 |
32 | Applicable altitudes | | <2000 | <2000 | <2000 | <3000 | <1000 |
33 | Motor operating mechanism | | | | | | |
34 | Model | | CJ2 | CJ2 | SRCJ2 | SRCJ2 | SRCJ2 |
35 | Motor voltage | V | AC 380 DC220 | AC 380 DC220 | AC 380 DC220 | AC 380 DC220 | AC 380 DC220 |
36 | Control circuit's voltage | V | AC 220 DC220 DC110 | AC 220 DC220 DC110 | AC 220 DC220 DC110 | AC 220 DC220 DC110 | AC 220 DC220 DC110 |
37 | Opening time and closing time | s | 7+1 | 7+1 | 16+1 | 16+1 | 16+1 |
38 | Output shaft rotation | | 180 | 180 | 180 | 180 | 180 |
39 | Manual operating mechanism | | | | | | |
40 | Model | | CS11 | CS11 | SRCS | SRCS | SRCS |
41 | control circuit voltage | V | AC 220 | AC 220 | AC 220 | AC 220 | AC 220 |
Product Categories : HV-Disconnect Switch
Premium Related Products
Other Products
Hot Products
Vs1-12 Series Indoor AC Vacuum Circuit BreakerOutdoor AC High-Voltage Disconnector SwitchLoad Break Switch Combination Fuse 12kv High Voltage Load Break SwitchTIANAN 12kv AC Metal-Clad Switchgear, High Voltage Electrical Switch Power Distribution Cabinet SwitchgearHigh Voltage Electrical Switch 12kv Indoor Sf6 Rum SwitchgearHigh Voltage 126kv Gis-Gas Insulated Switchgear (ZFW-126/T2500-40)Emergency Power Transmission/Distribution Movable Transformer Substation / 35kv~132kv Prefabricated Mobile Substation33kv Prefabricated Distribution Combined Substation Power Transmission/Supply Substation, Prefabricated Substation, Combined Substation220kv Power Transmission/Distribution Transformer Low Noise Oil Immersed Power TransformerOutdoor Hv Vacuum Circuit Breaker (ZW20-12)Indoor High Voltage Vacuum Circuit Breaker (VIB-12)Indoor High Voltage Vacuum Circuit Breaker with Lateral Operating Mechanism (VS1/R-12)Flexibar ConnectorVib-24 Indoor High Voltage Vacuum Circuit Breaker with Embedded PolesZw7-40.5 Outdoor Hv Vacuum Circuit Breaker with Central Operating MechanismVs1-12 Indoor High Voltage Vacuum Circuit Breaker