11kV prefabricated substation package substation combined substation

Basic Info

Model No.:  ZBW20 (JBW)-12

Product Description

Model NO.: ZBW20 (JBW)-12 Shell Material: Aluminum Alloy Installation: Fixed Current: AC Specification: 11kV HS Code: 8537109090 Certification: CCC, ISO9001 Voltage Level: Medium Voltage Structure: Floorstanding Trademark: TIANAN Origin: China         General
JBW (ZBW20)-12 series compact Prefabricated Substation is a kind of integrated complete power transmission and distribution equipment, used in 6~10KV, AC 50Hz system with a Transformer rated capacity of 50~1250KV. It is widely used in outdoor power supply fields, such as city high-rise building,residential zone,factory and mining,hotel,hospital,part,oil field,airport,wharf,market,and other temporary facilities, etc.
JBW(ZBW20)-12 series compact prefabricated Substation can be used in a close-ring-net for power distribution, but also in transformation power net for terminal power supply.

Service condition

Altitude: ≤1000m (above sea level)
Ambient temperature: Max. 40ºC  
                     Min. -30ºC   

Without any conductive dust and gas which will corrode the metal or broken insulation function;
Without any explosion danger field;
The gradient on installation spot shall be not more than 5°;
Relative humidity: Not exceed 90%
Outdoor wind speed : ≤35m/s;
Customer should negotiate with manufacturer if the service condition is different from above.


Structure characteristic

This product has the advantages of smaller volume,compact structure,high heat insulation and ventilation function,dust-proof,prevent small animal to enter,moist-proof,beautiful appearance and convenient to maintenance, we can choose cold-rolled steel plate,compound color plate and other material to make up enclosure.
All the black material of substation are taken surface anticorrosive treatment, it will guarantee that product will be not corroded for a long time.
HV side use HXGN26-12(F), with complete operation mistake prevention function.

Main technical parameters

Technical data of HXGN26-12(F) RMU (equipped with FN26-12 SF6 Load Switch), see table 1
Table 1

Name
Unit Parameter
Rated voltage kV 12
Rated frequency Hz 50
Rated current of main busbar A 630
Rated short time withstand current of main circuit and earth circuit kA/s 25/2
Rated peak withstand current of main circuit and earth circuit kA 63
Rated short circuit making current of main circuit and earth circuit kA 50
Full capacity breaking times of load switch Times 100
Fuse breaking current kA 31.5   40
Mechanical endurance Times 10000
1 min power frequency withstand voltage (r.m.s)
phase to earth,between phase/ isolating distance
kV 42/48
Lighting impulse withstand voltage(peak) 
phase to earth,between phase/ isolating distance
kV 75/85
Secondary circuit 1 min power frequency withstand voltage kV 2


Technical data of FN26-12 SF6 Load Switch, see table 2
Table 2

Name
Unit Parameter
Rated voltage kV 12
Rated current A 630
Rated frequency Hz 50
1 min power frequency withstand voltage (r.m.s)
phase to earth,between phase/ isolating distance
kV 42/48
Lighting impulse withstand voltage(peak)
phase to earth,between phase/ isolating distance
kV 75/85
Rated short time withstand current kA/s 25/2
Rated peak withstand current kA 63
Rated short circuit making current kA 50
Rated active load breaking current A/times 630/100
Rated cable charging current A 10
Rated un-load transformer breaking current
 
1600KVA transformer un-load current
Main circuit resistance µΩ ≤85
Rated SF6 gas pressure (in 20ºC) Mpa 0.04
Mechanical endurance Times 10000

Switch parameter on the LV side
Main switch adopts TANW1,MT series, shunt switch adopts TANM1,NSX series, see table 3
Table 3
Type Limit short circuit breaking capacity Icu (400V) KA Running short circuit breaking capacity Ics (400V) KA
TANW1-2000 80 50
MT08N1 42 42
MT10N1 42 42
MT12N1 42 42
MT20 65 65
TANM1-100S 35 17.5
TANM1-225S 35 17.5
TANM-400S 50 25
TANM-630S 50 25
TANM1-800S 75 50
NSX-100N 50 50
NSX-250N 50 50
NSX-400N 50 50
NSX-630N 50 50


HV & LV primary scheme

Substation HV primary scheme, see table 4
Substation LV primary typical scheme, see table 5

Structure and appearance

Substation base plate and supporting structure adopt U-steel and angle steel, it has higher mechanical intensity, product enclosure adopts cold-rolled steel plate or compound color plate, we can't see threaded connection or rivet connection from the exposed surface, so it has beautiful appearance.
Use clapboard to divide into independent room between each room of substation. Layout diagram see diagram 1.
In order to observe and maintain, LV room and HV room have lighting device.
Reversible connecting parts of substation adopt rubber belt to seal, with good damp-proof capacity.
HV room is equipped with HXGN26-12(F) RMU, and also with SF6 load switch,fuse(adopts Circuit Breaker if it required),lighting arrester,earth switch and mechanical interlock device, if adopts HV measuring, it is also equipped with voltage transformer,Current Transformer and measuring meter. ,,,,,,,,,,,,,,,,,
Each LV elements in LV room should be frontal arranged, instrument room on the top, it has observing window on the front, each element has independent and removable plate, convenient to maintain.
According to the requirement of reactive compensation, it should be equipped electric device, its capacity is 15~20% of transformer

Contact us if you need more details on Substation. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Transformer、Switchgear. If these products fail to match your need, please contact us and we would like to provide relevant information.